35 A at 75 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper6 AWG2.58 V (2.15%)
120 VAluminum4 AWG2.67 V (2.22%)
240 VCopper8 AWG4.01 V (1.67%)
240 VAluminum6 AWG4.24 V (1.77%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 35 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 35 amps at 75 feet?

At 240 V: 8 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances