Wire size for 35 amps at 50 feet

Advertisement

35 A at 50 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper8 AWG2.67 V (2.23%)
120 VAluminum6 AWG2.83 V (2.36%)
240 VCopper8 AWG2.67 V (1.11%)
240 VAluminum6 AWG2.83 V (1.18%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 35 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 35 amps at 50 feet?

At 240 V: 8 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.