Wire size for 100 amps at 300 feet

Advertisement

100 A at 300 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper250 kcmil3.09 V (2.57%)
120 VAluminum400 kcmil3.17 V (2.64%)
240 VCopper2/0 AWG5.80 V (2.42%)
240 VAluminum4/0 AWG6.00 V (2.50%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 100 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 100 amps at 300 feet?

At 240 V: 2/0 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.