WireMath

6 AWG voltage drop at 250 feet

Computed voltage drop for 6 AWG copper conductors on a 250 ft one-way run.

12.77 V

drop on 6 AWG copper, 250 ft one-way, 52 A load · 10.6% of 120 V · 5.3% of 240 V

6 AWG at 250 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
13 A3.19 V2.7%1.3%OK
26 A6.38 V5.3%2.7%OK
39 A9.57 V8.0%4.0%OK at 240 V up to 5%
52 A12.77 V10.6%5.3%Upsize

Vd = 2 × length × R × I ÷ 1000, R = 0.491 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 100 ft · 125 ft · 150 ft · 200 ft · 300 ft

FAQ

What is the voltage drop on 6 AWG wire at 250 feet?

At 52 A (80% of its 65 A 75°C rating) 6 AWG copper drops 12.77 V over 250 ft one-way: 10.6% at 120 V or 5.3% at 240 V.

How far can I run 6 AWG at 52 amps?

To stay within 3% at 120 V, about 70 ft one-way; at 240 V about 141 ft.