WireMath

6 AWG voltage drop at 125 feet

Computed voltage drop for 6 AWG copper conductors on a 125 ft one-way run.

6.38 V

drop on 6 AWG copper, 125 ft one-way, 52 A load · 5.3% of 120 V · 2.7% of 240 V

6 AWG at 125 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
13 A1.60 V1.3%0.7%OK
26 A3.19 V2.7%1.3%OK
39 A4.79 V4.0%2.0%OK
52 A6.38 V5.3%2.7%OK

Vd = 2 × length × R × I ÷ 1000, R = 0.491 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 100 ft · 150 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 6 AWG wire at 125 feet?

At 52 A (80% of its 65 A 75°C rating) 6 AWG copper drops 6.38 V over 125 ft one-way: 5.3% at 120 V or 2.7% at 240 V.

How far can I run 6 AWG at 52 amps?

To stay within 3% at 120 V, about 70 ft one-way; at 240 V about 141 ft.