WireMath

6 AWG voltage drop at 25 feet

Computed voltage drop for 6 AWG copper conductors on a 25 ft one-way run.

1.28 V

drop on 6 AWG copper, 25 ft one-way, 52 A load · 1.1% of 120 V · 0.5% of 240 V

6 AWG at 25 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
13 A0.32 V0.3%0.1%OK
26 A0.64 V0.5%0.3%OK
39 A0.96 V0.8%0.4%OK
52 A1.28 V1.1%0.5%OK

Vd = 2 × length × R × I ÷ 1000, R = 0.491 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

50 ft · 75 ft · 100 ft · 125 ft · 150 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 6 AWG wire at 25 feet?

At 52 A (80% of its 65 A 75°C rating) 6 AWG copper drops 1.28 V over 25 ft one-way: 1.1% at 120 V or 0.5% at 240 V.

How far can I run 6 AWG at 52 amps?

To stay within 3% at 120 V, about 70 ft one-way; at 240 V about 141 ft.