2 AWG voltage drop at 25 feet
Computed voltage drop for 2 AWG copper conductors on a 25 ft one-way run.
0.89 V
drop on 2 AWG copper, 25 ft one-way, 92 A load · 0.7% of 120 V · 0.4% of 240 V
2 AWG at 25 ft by load
| Load | Drop | % at 120 V | % at 240 V | 3% rule (240 V) |
|---|---|---|---|---|
| 23 A | 0.22 V | 0.2% | 0.1% | OK |
| 46 A | 0.45 V | 0.4% | 0.2% | OK |
| 69 A | 0.67 V | 0.6% | 0.3% | OK |
| 92 A | 0.89 V | 0.7% | 0.4% | OK |
Vd = 2 × length × R × I ÷ 1000, R = 0.194 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.
Same wire, other distances
50 ft · 75 ft · 100 ft · 125 ft · 150 ft · 200 ft · 250 ft · 300 ft
FAQ
What is the voltage drop on 2 AWG wire at 25 feet?
At 92 A (80% of its 115 A 75°C rating) 2 AWG copper drops 0.89 V over 25 ft one-way: 0.7% at 120 V or 0.4% at 240 V.
How far can I run 2 AWG at 92 amps?
To stay within 3% at 120 V, about 101 ft one-way; at 240 V about 202 ft.