2 AWG voltage drop at 125 feet

Computed voltage drop for 2 AWG copper conductors on a 125 ft one-way run.

4.46 V

drop on 2 AWG copper, 125 ft one-way, 92 A load · 3.7% of 120 V · 1.9% of 240 V

2 AWG at 125 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
23 A1.12 V0.9%0.5%OK
46 A2.23 V1.9%0.9%OK
69 A3.35 V2.8%1.4%OK
92 A4.46 V3.7%1.9%OK

Vd = 2 × length × R × I ÷ 1000, R = 0.194 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 100 ft · 150 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 2 AWG wire at 125 feet?

At 92 A (80% of its 115 A 75°C rating) 2 AWG copper drops 4.46 V over 125 ft one-way: 3.7% at 120 V or 1.9% at 240 V.

How far can I run 2 AWG at 92 amps?

To stay within 3% at 120 V, about 101 ft one-way; at 240 V about 202 ft.