WireMath

2 AWG voltage drop at 200 feet

Computed voltage drop for 2 AWG copper conductors on a 200 ft one-way run.

7.14 V

drop on 2 AWG copper, 200 ft one-way, 92 A load · 5.9% of 120 V · 3.0% of 240 V

2 AWG at 200 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
23 A1.78 V1.5%0.7%OK
46 A3.57 V3.0%1.5%OK
69 A5.35 V4.5%2.2%OK
92 A7.14 V5.9%3.0%OK

Vd = 2 × length × R × I ÷ 1000, R = 0.194 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 100 ft · 125 ft · 150 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 2 AWG wire at 200 feet?

At 92 A (80% of its 115 A 75°C rating) 2 AWG copper drops 7.14 V over 200 ft one-way: 5.9% at 120 V or 3.0% at 240 V.

How far can I run 2 AWG at 92 amps?

To stay within 3% at 120 V, about 101 ft one-way; at 240 V about 202 ft.