WireMath

2/0 AWG voltage drop at 75 feet

Computed voltage drop for 2/0 AWG copper conductors on a 75 ft one-way run.

2.03 V

drop on 2/0 AWG copper, 75 ft one-way, 140 A load · 1.7% of 120 V · 0.8% of 240 V

2/0 AWG at 75 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
35 A0.51 V0.4%0.2%OK
70 A1.02 V0.8%0.4%OK
105 A1.52 V1.3%0.6%OK
140 A2.03 V1.7%0.8%OK

Vd = 2 × length × R × I ÷ 1000, R = 0.0967 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 100 ft · 125 ft · 150 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 2/0 AWG wire at 75 feet?

At 140 A (80% of its 175 A 75°C rating) 2/0 AWG copper drops 2.03 V over 75 ft one-way: 1.7% at 120 V or 0.8% at 240 V.

How far can I run 2/0 AWG at 140 amps?

To stay within 3% at 120 V, about 133 ft one-way; at 240 V about 266 ft.