WireMath

2/0 AWG voltage drop at 100 feet

Computed voltage drop for 2/0 AWG copper conductors on a 100 ft one-way run.

2.71 V

drop on 2/0 AWG copper, 100 ft one-way, 140 A load · 2.3% of 120 V · 1.1% of 240 V

2/0 AWG at 100 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
35 A0.68 V0.6%0.3%OK
70 A1.35 V1.1%0.6%OK
105 A2.03 V1.7%0.8%OK
140 A2.71 V2.3%1.1%OK

Vd = 2 × length × R × I ÷ 1000, R = 0.0967 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 125 ft · 150 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 2/0 AWG wire at 100 feet?

At 140 A (80% of its 175 A 75°C rating) 2/0 AWG copper drops 2.71 V over 100 ft one-way: 2.3% at 120 V or 1.1% at 240 V.

How far can I run 2/0 AWG at 140 amps?

To stay within 3% at 120 V, about 133 ft one-way; at 240 V about 266 ft.