WireMath

2/0 AWG voltage drop at 200 feet

Computed voltage drop for 2/0 AWG copper conductors on a 200 ft one-way run.

5.42 V

drop on 2/0 AWG copper, 200 ft one-way, 140 A load · 4.5% of 120 V · 2.3% of 240 V

2/0 AWG at 200 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
35 A1.35 V1.1%0.6%OK
70 A2.71 V2.3%1.1%OK
105 A4.06 V3.4%1.7%OK
140 A5.42 V4.5%2.3%OK

Vd = 2 × length × R × I ÷ 1000, R = 0.0967 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 100 ft · 125 ft · 150 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 2/0 AWG wire at 200 feet?

At 140 A (80% of its 175 A 75°C rating) 2/0 AWG copper drops 5.42 V over 200 ft one-way: 4.5% at 120 V or 2.3% at 240 V.

How far can I run 2/0 AWG at 140 amps?

To stay within 3% at 120 V, about 133 ft one-way; at 240 V about 266 ft.