25 A at 250 ft one-way

VoltageConductorMinimum sizeVoltage drop
120 VCopper3 AWG3.06 V (2.55%)
120 VAluminum1 AWG3.16 V (2.64%)
240 VCopper6 AWG6.14 V (2.56%)
240 VAluminum4 AWG6.35 V (2.65%)

Smallest size meeting NEC 75 °C ampacity (with 240.4(D) limits) and ≤3% drop at the full 25 A. Use 125% sizing for continuous loads; apply derating for more than 3 current-carrying conductors or high ambient temperature.

Adjust the numbers

FAQ

What size wire for 25 amps at 250 feet?

At 240 V: 6 AWG copper keeps voltage drop under 3%. See the table for 120 V and aluminum.

Same current, other distances