2.90 V

drop on 10 AWG copper, 50 ft one-way, 24 A load · 2.4% of 120 V · 1.2% of 240 V

10 AWG at 50 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
6 A0.73 V0.6%0.3%OK
12 A1.45 V1.2%0.6%OK
18 A2.18 V1.8%0.9%OK
24 A2.90 V2.4%1.2%OK

Vd = 2 × length × R × I ÷ 1000, R = 1.21 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 75 ft · 100 ft · 125 ft · 150 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 10 AWG wire at 50 feet?

At 24 A (80% of its 30 A 75°C rating) 10 AWG copper drops 2.90 V over 50 ft one-way: 2.4% at 120 V or 1.2% at 240 V.

How far can I run 10 AWG at 24 amps?

To stay within 3% at 120 V, about 62 ft one-way; at 240 V about 124 ft.