WireMath

10 AWG voltage drop at 125 feet

Computed voltage drop for 10 AWG copper conductors on a 125 ft one-way run.

7.26 V

drop on 10 AWG copper, 125 ft one-way, 24 A load · 6.0% of 120 V · 3.0% of 240 V

10 AWG at 125 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
6 A1.81 V1.5%0.8%OK
12 A3.63 V3.0%1.5%OK
18 A5.45 V4.5%2.3%OK
24 A7.26 V6.0%3.0%OK at 240 V up to 5%

Vd = 2 × length × R × I ÷ 1000, R = 1.21 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 100 ft · 150 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 10 AWG wire at 125 feet?

At 24 A (80% of its 30 A 75°C rating) 10 AWG copper drops 7.26 V over 125 ft one-way: 6.0% at 120 V or 3.0% at 240 V.

How far can I run 10 AWG at 24 amps?

To stay within 3% at 120 V, about 62 ft one-way; at 240 V about 124 ft.