WireMath

8 AWG voltage drop at 250 feet

Computed voltage drop for 8 AWG copper conductors on a 250 ft one-way run.

15.28 V

drop on 8 AWG copper, 250 ft one-way, 40 A load · 12.7% of 120 V · 6.4% of 240 V

8 AWG at 250 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
10 A3.82 V3.2%1.6%OK
20 A7.64 V6.4%3.2%OK at 240 V up to 5%
30 A11.46 V9.6%4.8%OK at 240 V up to 5%
40 A15.28 V12.7%6.4%Upsize

Vd = 2 × length × R × I ÷ 1000, R = 0.764 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 100 ft · 125 ft · 150 ft · 200 ft · 300 ft

FAQ

What is the voltage drop on 8 AWG wire at 250 feet?

At 40 A (80% of its 50 A 75°C rating) 8 AWG copper drops 15.28 V over 250 ft one-way: 12.7% at 120 V or 6.4% at 240 V.

How far can I run 8 AWG at 40 amps?

To stay within 3% at 120 V, about 59 ft one-way; at 240 V about 118 ft.