WireMath

1/0 AWG voltage drop at 100 feet

Computed voltage drop for 1/0 AWG copper conductors on a 100 ft one-way run.

2.93 V

drop on 1/0 AWG copper, 100 ft one-way, 120 A load · 2.4% of 120 V · 1.2% of 240 V

1/0 AWG at 100 ft by load

LoadDrop% at 120 V% at 240 V3% rule (240 V)
30 A0.73 V0.6%0.3%OK
60 A1.46 V1.2%0.6%OK
90 A2.20 V1.8%0.9%OK
120 A2.93 V2.4%1.2%OK

Vd = 2 × length × R × I ÷ 1000, R = 0.122 Ω/1000 ft (copper, NEC Ch. 9 Table 8). Aluminum is about 1.6× higher.

Same wire, other distances

25 ft · 50 ft · 75 ft · 125 ft · 150 ft · 200 ft · 250 ft · 300 ft

FAQ

What is the voltage drop on 1/0 AWG wire at 100 feet?

At 120 A (80% of its 150 A 75°C rating) 1/0 AWG copper drops 2.93 V over 100 ft one-way: 2.4% at 120 V or 1.2% at 240 V.

How far can I run 1/0 AWG at 120 amps?

To stay within 3% at 120 V, about 123 ft one-way; at 240 V about 246 ft.