7.5 kVA to amps
Full-load current for transformers and generators.
9.0 A
7.5 kVA at 480 V three-phase · 20.8 A at 208 V three-phase · 31.2 A at 240 V single-phase
7.5 kVA full-load current
| Voltage | Amps |
|---|---|
| 120 V single-phase | 62.5 A |
| 240 V single-phase | 31.2 A |
| 208 V three-phase | 20.8 A |
| 240 V three-phase | 18.0 A |
| 480 V three-phase | 9.0 A |
| 600 V three-phase | 7.2 A |
Single-phase I = kVA × 1000 ÷ V; three-phase I = kVA × 1000 ÷ (√3 × V).
FAQ
How many amps is a 7.5 kVA transformer?
31.2 A at 240 V single-phase, 20.8 A at 208 V three-phase and 9.0 A at 480 V three-phase.
How many kW is 7.5 kVA?
At a 0.8 power factor 7.5 kVA is 6 kW; at unity power factor it equals 7.5 kW.