WireMath

50 hp motor: how many amps?

Full-load current from NEC Article 430 tables.

130 A

50 hp motor full-load current at 230 V three-phase · 37.30 kW output

Full-load current by voltage

SupplyFull-load ampsConductor ampacity (125%)
208 V three-phase143 A178.8 A
230 V three-phase130 A162.5 A
460 V three-phase65.0 A81.2 A

NEC 430.248/430.250 table values for typical induction motors; use these (not the nameplate) to size conductors and short-circuit protection, and the nameplate for overload protection.

FAQ

How many amps does a 50 hp motor draw?

Per NEC tables, 143 A A at 208 V three-phase; 130 A A at 230 V three-phase; 65.0 A A at 460 V three-phase.

How many watts is 50 hp?

50 hp = 37300 W of mechanical output. Electrical input is higher because of motor efficiency and power factor.