WireMath

5 hp motor: how many amps?

Full-load current from NEC Article 430 tables.

28 A

5 hp motor full-load current at 230 V single-phase · 3.73 kW output

Full-load current by voltage

SupplyFull-load ampsConductor ampacity (125%)
115 V single-phase56 A70.0 A
230 V single-phase28 A35.0 A
208 V three-phase16.7 A20.9 A
230 V three-phase15.2 A19.0 A
460 V three-phase7.6 A9.5 A

NEC 430.248/430.250 table values for typical induction motors; use these (not the nameplate) to size conductors and short-circuit protection, and the nameplate for overload protection.

FAQ

How many amps does a 5 hp motor draw?

Per NEC tables, 56 A A at 115 V single-phase; 28 A A at 230 V single-phase; 16.7 A A at 208 V three-phase; 15.2 A A at 230 V three-phase; 7.6 A A at 460 V three-phase.

How many watts is 5 hp?

5 hp = 3730 W of mechanical output. Electrical input is higher because of motor efficiency and power factor.