WireMath

40 hp motor: how many amps?

Full-load current from NEC Article 430 tables.

104 A

40 hp motor full-load current at 230 V three-phase · 29.84 kW output

Full-load current by voltage

SupplyFull-load ampsConductor ampacity (125%)
208 V three-phase114 A142.5 A
230 V three-phase104 A130.0 A
460 V three-phase52.0 A65.0 A

NEC 430.248/430.250 table values for typical induction motors; use these (not the nameplate) to size conductors and short-circuit protection, and the nameplate for overload protection.

FAQ

How many amps does a 40 hp motor draw?

Per NEC tables, 114 A A at 208 V three-phase; 104 A A at 230 V three-phase; 52.0 A A at 460 V three-phase.

How many watts is 40 hp?

40 hp = 29840 W of mechanical output. Electrical input is higher because of motor efficiency and power factor.