WireMath

3/4 hp motor: how many amps?

Full-load current from NEC Article 430 tables.

6.9 A

3/4 hp motor full-load current at 230 V single-phase · 0.56 kW output

Full-load current by voltage

SupplyFull-load ampsConductor ampacity (125%)
115 V single-phase13.8 A17.2 A
230 V single-phase6.9 A8.6 A
208 V three-phase3.5 A4.4 A
230 V three-phase3.2 A4.0 A
460 V three-phase1.6 A2.0 A

NEC 430.248/430.250 table values for typical induction motors; use these (not the nameplate) to size conductors and short-circuit protection, and the nameplate for overload protection.

FAQ

How many amps does a 3/4 hp motor draw?

Per NEC tables, 13.8 A A at 115 V single-phase; 6.9 A A at 230 V single-phase; 3.5 A A at 208 V three-phase; 3.2 A A at 230 V three-phase; 1.6 A A at 460 V three-phase.

How many watts is 3/4 hp?

3/4 hp = 560 W of mechanical output. Electrical input is higher because of motor efficiency and power factor.