Full-load current from NEC Article 430 tables.

68 A

25 hp motor full-load current at 230 V three-phase · 18.65 kW output

Full-load current by voltage

SupplyFull-load ampsConductor ampacity (125%)
208 V three-phase74.8 A93.5 A
230 V three-phase68 A85.0 A
460 V three-phase34.0 A42.5 A

NEC 430.248/430.250 table values for typical induction motors; use these (not the nameplate) to size conductors and short-circuit protection, and the nameplate for overload protection.

FAQ

How many amps does a 25 hp motor draw?

Per NEC tables, 74.8 A A at 208 V three-phase; 68 A A at 230 V three-phase; 34.0 A A at 460 V three-phase.

How many watts is 25 hp?

25 hp = 18650 W of mechanical output. Electrical input is higher because of motor efficiency and power factor.