WireMath

15 hp motor: how many amps?

Full-load current from NEC Article 430 tables.

42 A

15 hp motor full-load current at 230 V three-phase · 11.19 kW output

Full-load current by voltage

SupplyFull-load ampsConductor ampacity (125%)
208 V three-phase46.2 A57.8 A
230 V three-phase42 A52.5 A
460 V three-phase21.0 A26.2 A

NEC 430.248/430.250 table values for typical induction motors; use these (not the nameplate) to size conductors and short-circuit protection, and the nameplate for overload protection.

FAQ

How many amps does a 15 hp motor draw?

Per NEC tables, 46.2 A A at 208 V three-phase; 42 A A at 230 V three-phase; 21.0 A A at 460 V three-phase.

How many watts is 15 hp?

15 hp = 11190 W of mechanical output. Electrical input is higher because of motor efficiency and power factor.