1 hp motor: how many amps?
Full-load current from NEC Article 430 tables.
8 A
1 hp motor full-load current at 230 V single-phase · 0.75 kW output
Full-load current by voltage
| Supply | Full-load amps | Conductor ampacity (125%) |
|---|---|---|
| 115 V single-phase | 16 A | 20.0 A |
| 230 V single-phase | 8 A | 10.0 A |
| 208 V three-phase | 4.6 A | 5.8 A |
| 230 V three-phase | 4.2 A | 5.2 A |
| 460 V three-phase | 2.1 A | 2.6 A |
NEC 430.248/430.250 table values for typical induction motors; use these (not the nameplate) to size conductors and short-circuit protection, and the nameplate for overload protection.
FAQ
How many amps does a 1 hp motor draw?
Per NEC tables, 16 A A at 115 V single-phase; 8 A A at 230 V single-phase; 4.6 A A at 208 V three-phase; 4.2 A A at 230 V three-phase; 2.1 A A at 460 V three-phase.
How many watts is 1 hp?
1 hp = 746 W of mechanical output. Electrical input is higher because of motor efficiency and power factor.