WireMath

1 hp motor: how many amps?

Full-load current from NEC Article 430 tables.

8 A

1 hp motor full-load current at 230 V single-phase · 0.75 kW output

Full-load current by voltage

SupplyFull-load ampsConductor ampacity (125%)
115 V single-phase16 A20.0 A
230 V single-phase8 A10.0 A
208 V three-phase4.6 A5.8 A
230 V three-phase4.2 A5.2 A
460 V three-phase2.1 A2.6 A

NEC 430.248/430.250 table values for typical induction motors; use these (not the nameplate) to size conductors and short-circuit protection, and the nameplate for overload protection.

FAQ

How many amps does a 1 hp motor draw?

Per NEC tables, 16 A A at 115 V single-phase; 8 A A at 230 V single-phase; 4.6 A A at 208 V three-phase; 4.2 A A at 230 V three-phase; 2.1 A A at 460 V three-phase.

How many watts is 1 hp?

1 hp = 746 W of mechanical output. Electrical input is higher because of motor efficiency and power factor.