WireMath

1/3 hp motor: how many amps?

Full-load current from NEC Article 430 tables.

3.6 A

1/3 hp motor full-load current at 230 V single-phase · 0.25 kW output

Full-load current by voltage

SupplyFull-load ampsConductor ampacity (125%)
115 V single-phase7.2 A9.0 A
230 V single-phase3.6 A4.5 A

NEC 430.248/430.250 table values for typical induction motors; use these (not the nameplate) to size conductors and short-circuit protection, and the nameplate for overload protection.

FAQ

How many amps does a 1/3 hp motor draw?

Per NEC tables, 7.2 A A at 115 V single-phase; 3.6 A A at 230 V single-phase.

How many watts is 1/3 hp?

1/3 hp = 249 W of mechanical output. Electrical input is higher because of motor efficiency and power factor.