WireMath

1/2 hp motor: how many amps?

Full-load current from NEC Article 430 tables.

4.9 A

1/2 hp motor full-load current at 230 V single-phase · 0.37 kW output

Full-load current by voltage

SupplyFull-load ampsConductor ampacity (125%)
115 V single-phase9.8 A12.2 A
230 V single-phase4.9 A6.1 A
208 V three-phase2.4 A3.0 A
230 V three-phase2.2 A2.8 A
460 V three-phase1.1 A1.4 A

NEC 430.248/430.250 table values for typical induction motors; use these (not the nameplate) to size conductors and short-circuit protection, and the nameplate for overload protection.

FAQ

How many amps does a 1/2 hp motor draw?

Per NEC tables, 9.8 A A at 115 V single-phase; 4.9 A A at 230 V single-phase; 2.4 A A at 208 V three-phase; 2.2 A A at 230 V three-phase; 1.1 A A at 460 V three-phase.

How many watts is 1/2 hp?

1/2 hp = 373 W of mechanical output. Electrical input is higher because of motor efficiency and power factor.